Fan coil error code guide

Fan coils with electronic controls report faults with a code on the display or by flashing an LED on the control board. Below are the codes we have compiled from manufacturers' documentation, plus a symptom-based diagnosis table for units without codes.

  • From manufacturer documentation
  • Organised by brand
  • LED and display codes
  • Symptom-based diagnosis
In short: a fan coil error code is a code shown on the controller display of electronically controlled fan coils, indicating a sensor, water temperature, drain/pump, communication or board problem. The same code can mean different things depending on the brand and controller model. This page contains the code lists for Daikin, Carrier, Aermec, Galletti, Sabiana and McQuay, and a diagnostic method for units without codes.
Important: the same code can mean different things on different controllers and boards. Sending us a photo of the code and the unit's rating plate is the safest way to a correct diagnosis. Isolate the power before touching any electrical parts.

Brands with a code list

Daikin fan coil error codes

FWT wall-mounted, FWC cassette, FWF and FWG series (wired controller display)

When an abnormality occurs, the wired controller shows the error code by flashing it.

Code / indicationMeaningWhat to do
E1Room (ambient) temperature sensor fault: open or short circuitCheck the sensor socket and cable; replace the sensor if necessary.
E2Water pipe / coil temperature sensor faultThe sensor connection and resistance are measured; the sensor is replaced if necessary.
E4Water temperature not suitable (insufficient)The chiller or boiler outlet water, valve and circulation are checked.
E5Incorrect water temperatureThe water supply, 3-way valve and heating/cooling mode selection are checked.
E6Drain (condensate) pump fault (cassette)The drain line and float are cleaned and the pump is tested.
E8Hardware fault: short-circuited button on the boardThe display or control board needs replacing.
E9No feedback from the indoor fan motor (FWT)The fan motor connector is checked; the motor or board is replaced.

European series (FWV, FWL, FWM, FWZ, FWR, FWS, FWB, FWD) – FWEC control board

This series has no numbered error codes. If the water temperature does not suit the mode (e.g. lukewarm water in cooling), the mode symbol on the controller flashes. Fix: check the chiller/boiler and the water temperature.

Daikin fan coil service page →

Carrier fan coil error codes

Carrier 42GW cassette – HDB control board

The red LED on the board flashes as many times as the fault number (0.5 s on / 0.5 s off, followed by a 5 s pause).

Code / indicationMeaningWhat to do
2 flashesAir temperature sensor faultThe sensor and socket are checked and replaced if necessary.
3 flashesWater (changeover) sensor faultThe water sensor connection and its position on the pipe are checked.
4 flashesCold draught thermistor faultThe thermistor is checked or replaced.
5 flashesCondensate pump faultThe drain line and float are cleaned and the pump is checked.
6 flashesElectric heater configuration errorBoard settings (DIP switches / parameters) are corrected.
7 flashesBoard memory (EEPROM) errorThe control board needs replacing.
8 flashesChilled beam configuration errorThe configuration is corrected.

Carrier 42N series – electronic control

Faults are indicated by the colour of the LEDs on the board.

Code / indicationMeaningWhat to do
Red LED flashingSensor fault: room sensor or water temperature sensor faulty or short-circuitedThe sensors are measured and the faulty one is replaced.
Yellow LED flashingConfiguration error: central changeover signals active at the same timeWiring and settings are corrected.

Carrier 42TPM

If there is more than one fault, the codes are shown in sequence.

Code / indicationMeaningWhat to do
E1Room sensor faultThe sensor is checked or replaced.
E2Coil sensor faultThe sensor is checked or replaced.

Carrier fan coil service page →

Aermec fan coil error codes

VMF system (FCZ, FCZI, FCXI, VED, Omnia) – VMF-E4X controller display

Code / indicationMeaningWhat to do
AL 1No communication between the controller and the fan coil thermostat (E0/E1)The communication cable, polarity and power supply are checked.
AL 2Inverter (EC fan) board faultThe LEDs on the inverter board in the fan coil are checked.
AL 3Room sensor in the controller faultyThe system switches to the sensor on the fan coil; the controller is serviced.

FCXI inverter board

The board has alarm and power LEDs. Alarm types: high temperature, overvoltage, undervoltage, overcurrent, overload, safety. If an alarm lasts longer than 1.5 minutes it becomes permanent; it is reset by switching the power off and on again.

Aermec fan coil service page →

Galletti fan coil error codes

EVO / EVO-2-TOUCH controller

Instead of numbered codes, "probe alarm" (air or water sensor) and "no RS485 communication" warnings are shown. Fix: check the probe wiring and polarity, the board power supply (STATUS LED) and the RS485 line.

Galletti fan coil service page →

Sabiana fan coil error codes

Carisma (ECM) – status warnings

This series uses LED warnings instead of numbered codes: T1 sensor fault, T3 sensor above 70 °C, window contact open, pump alarm. If there is more than one event, two LEDs flash together.

Sabiana fan coil service page →

McQuay fan coil error codes

McQuay MFU-C – AC2800 electronic controller

Faults are indicated by the number of LED flashes.

Code / indicationMeaningWhat to do
5 flashesFan coil mode and water temperature do not match (e.g. cold water in heating mode)The mode selection and chiller/boiler status are checked.
7 flashesAmbient temperature sensor malfunctioningThe sensor is checked or replaced.
8 flashesWater temperature sensor malfunctioningThe sensor is checked or replaced.

McQuay fan coil service page →

Thermostat alerts (Siemens RDF series)

IndicationMeaningWhat to do
AL1External fault input X1 active (e.g. condensate alarm)The device connected to input X1 is checked.
AL2External fault input X2 activeThe device connected to input X2 is checked.
FILFilter cleaning reminderThe filter is cleaned and the alert reset.
Dew (condensation) symbolCondensation detected in the room, cooling stoppedHumidity and water temperature are checked.

Diagnosis on fan coils without error codes

Many fan coils, such as Aldağ, Üntes, Form and Airfel, run with a 3-speed motor and a simple thermostat and have no error codes. Diagnosis is based on symptoms and measurements:

SymptomPossible causeDetails
Leaking waterBlocked drain, full/cracked drain pan, sweating valveSolution
Not cooling / not heatingStuck motorized valve, air in the coil, dirty filterSolution
Fan not runningCapacitor, motor, speed controlSolution
Room always cold/hotValve stuck open or closedSolution
Controller not respondingThermostat, sensor, wiringSolution

What the code groups generally mean

Sensor codes

Indicate that the room, water or coil sensor is open or short-circuited. Usually the sensor or its socket is replaced.

Water temperature codes

Indicate that the incoming water does not suit the selected mode. The problem is often in the chiller, boiler or valve.

Drain / pump codes

A float or pump alarm on cassette and concealed ceiling units. The drain pan and drain line are checked.

Communication and board codes

No communication between the controller and the board, or a faulty board memory. Wiring and the board are checked.

Sources: manufacturers' user and service manuals; the sources for each brand are listed in its own section and on the brand page.

Frequently asked questions

What does a fan coil E1 error mean?

On units such as Daikin and Carrier 42TPM, E1 indicates a room temperature sensor fault. The sensor or its socket is checked and replaced if necessary. The meaning of a code can vary by controller.

How is a fan coil condensate pump error fixed?

The drain pan and drain line are cleaned, the float is checked to make sure it moves freely and the pump is tested. If the pump has failed, it is replaced.

My fan coil shows no code but does not work. What should I do?

First check the breaker and the controller. If the problem persists, send us the symptom and the unit's rating plate and we will diagnose it with measurements.